Magnetic Surface Temperature Sensor Radio

Magnetic Surface Temperature Sensor Radio

Typ: METS-WRM | ID: YA

technical features

  • Input: RTD Pt100 (maximum range -50...+400 °C)
  • Output: Radio transceiver
  • Voltage supply: Lithium-ion battery pack
  • Accuracy: ca. 0,2% FS
  • Process connection: clamping magnet
  • Electrical connection: Without / M12x1, 4-pole (charge, supply)
  • Radio range: internal antenna 20 m / external antenna 100 m radio
  • Temperature range: -20...+45...60 °C (ambient)
  • Configuration: Factory setting
  • Material: Stainless steel 1.5471 (medium contact)
  • Protection: At least IP65

Magnetic Surface Temperature Sensor

Magnetic Surface Temperature Sensor *'*

Typ: METS-WTM | ID: NW

technical features

  • Input: RTD Pt100 (maximum range -50...+200 °C)
  • Output: 4...20 mA current loop (2-wire)
  • Voltage supply: out of current loop (12...40 VDC)
  • Accuracy: see technical details
  • Process connection: clamping magnet
  • Electrical connection: several plugs
  • Temperature range: -20...+80 °C (ambient)
  • Limit value contacts: 2 electronically (NPN / PNP)
  • Adjustment: software
  • Material: stainless steel 1.4571 (medium contact)
  • Protection: at least IP65

Magnetic Surface Temperature Sensor

Magnetic Surface Temperature Sensor *'*

Typ: METS-WSM | ID: NX

technical features

  • Input: RTD Pt100 (maximum range -50...+200 °C)
  • Output: 4...20 mA current loop (2-wire)
  • Voltage supply: out of current loop (12...40 VDC)
  • Accuracy: see technical details
  • Process connection: clamping magnet
  • Electrical connection: several plugs
  • Temperature range: -20...+80 °C (ambient)
  • Limit value contacts: 2 electronically (NPN / PNP)
  • Adjustment: keys / software
  • Material: stainless steel 1.5471 (medium contact)
  • Protection: at least IP65

Low Profile Load Cell Assembly

Low Profile Load Cell Assembly

type: SILO-V | ID: LP

technical features

  • Ranges: 0...1000 up to 0...30000 kg
  • Output: 2,0 ±0,1% mV/V
  • Voltage supply: 10 VDC (standard)
  • Accuracy: < ±0,05% of range (combined error)
  • Output resistance: 700 ±5 Ω
  • Temperature range: -30...+70 °C (working)
  • Insulation resistance: > 5000 MΩ
  • Safe overload: 150% of range
  • Material load cell: stainless steel 1.4021 / AISI 420
  • Protection: IP68
  • Cable length: standard 10 m

Pressure transmitter SIL

Pressure transmitter SIL

type: PT-SIL | ID: UI

technical features


  • Ranges: 0...0,1 bar up to 0...1000 bar / -1...+24 bar
  • Output: Current / Voltage / Ratiometric
  • Supply: see data sheet
  • Accuracy: 0,5% (0,25%)of span
  • Degree of protection: IP67 (IP65 with valve plug)
  • Casing: 316Ti-steel
  • Process connection: G 1/2, G 1/4, 1/2 NPT, 1/4 NPT
  • Connection: See data sheet