Other Devices
Signal Converter Current / Voltage / Switch
Typ: PCV20 | ID: PH
Technical Features
- Input: 3x Current / 3x Voltage
- Output: Analog / Pulse / Switch
- Supply: 24 VDC (max. 12…35 VDC)
- Current consumption: max. 4 VA
- Galvanic isolation: Yes
- Accuracy: see technical data
- Electrical connection: 4 plug-in terminal strips, 4-pole
- Operating temperature: -20…+60 °C
- Humidity: max. 90% rH, non-condensing
- EMC: EN ISO 50081-1 / EN ISO 50082-2
- Safety: EN ISO 60730-1
Strain Gauge Overload Protection PLc
Type: PS-SIL | ID: SV
Technical Features
- Input: max. ±3 VDC
- Output: max. 30 VAC / VDC at max. 500 mA
- Supply: 18…36 VDC at max. 15 mA
- Strain gauge supply: 0,5…5 VDC
- Limit value: 0,5…8,2 +-0,05 mV
- Accuracy: ±50 µV
- Response time: 50 ms
- Connection: Soldering pads
- Material: FR4, PBT
- Protection class: IP00
- Approval: PLc / SIL1
Configurator Modem Analog
Type: DEV-KMA | ID: DK
Technical Features
- PC interface: virtual serial port
- Supply: out of USB connection
- Current consumption: max. 350 mA
- Connection transmitter: alligator clamps / M12, 4-pole
- Connection PC: USB type A
- Connection multimeter: bunch plugs
- USB specification: 2.0 compatible
- Protection: IP20
- Case: ABS, 82x51x17 mm
- Operating systems: Windows XP , Win 7, Win 8, Win 10
- Software (included): TrComm
Converter for potentiometer *'*
type: DRMU-S2 - DRPO-S2 | ID: DR series 2
technical features
- Input: 3,3 kΩ
- Measuring current: 0,15 mA
- Output: 4...20 mA current loop
- Supply: Current loop
- Electrical connection: 2...6 plug-in terminal strip
- Limit vale contacts: without
- Protection: IP20
- Accuracy: see data sheet
- Enclosure: for DIN rail
Converter for resistance *'*
type: DRMU-S2 - DRWI-S2 | ID: DR series 2
technical features
- Input: 3,3 kΩ
- Measuring current: 0,15 mA
- Output: 4...20 mA current loop
- Supply: Current loop
- Electrical connection: 2...6 plug-in terminal strip
- Limit vale contacts: without
- Protection: IP20
- Accuracy: see data sheet
- Enclosure: for DIN rail
Converter for potentiometer *'*
type: DRMU-S4 - DRPO-S4 | ID: DR series 4
technical features
- Input: 3,3 kΩ
- Measuring current: 0,15 mA
- Output: 4...20 mA current loop
- Supply: 24 VDC, 85...250 VAC, current loop
- Electrical connection: 2...6 plug-in terminal strip
- Limit vale contacts: 2x electronically,
2x relays - Protection: IP20
- Accuracy: see data sheet
- Enclosure: for DIN rail
Converter for resistance *'*
type: DRMU-S4 - DRWI-S4 | ID: DR series 4
technical features
- Input: 3,3 kΩ
- Measuring current: 0,15 mA
- Output: 4...20 mA current loop
- Supply: 24 VDC, 85...250 VAC, current loop
- Electrical connection: 2...6 plug-in terminal strip
- Limit vale contacts: 2x electronically,
2x relays - Protection: IP20
- Accuracy: see data sheet
- Enclosure: for DIN rail
Analog Summing Amplifier 4-Channel
type: DR-AS4K | ID: ▒
technical features
- Function: Arithmetic mean of input signals
- Input: 2...4x 4...20 mA
- Output: 1x 4...20 mA
- Supply: 24 VDC
- Current consumption: ca. 50 mA (without input signals)
- Connection: 4 plug-in terminal stips, 4-pole
- Temperature range: -10...60 °C (ambient)
- Protection: IP20
- Enclosure: DR22,5 made of PA66 GF30
HART-Modem USB
Type: DEV-HM | ID: --
technical features
- Active operation: current loop is supplied too
- Passive operation: used in an existing current loop
- PC interface: virtual serial port
- Supply: out of USB connection
- USB specification: 2.0 compatiblel
- Protection: IP20
- Galvanical insulation: between USB and HART
- Case: ABS, 105x66x20 mm
Digital video signal switch
Typ: DVU | ID: VU
technical features
- 4-channel video signal switch
- Channel selection "Auto" / "Manual" / "Digital"
- Switch-over time of the four channels in auto-mode adjustable
- BNC-jacks for inputs and output
- Supply: 115/230 VAC, 24 VAC/DC, galvanic separation
4-input summing amplifier
type: ASV | ID: SU
technical features
- 4 inputs 0(4)...20mA, 0...10V, selectable by DIP-switches
- Adding of input signals
- Output, 0(4)...20mA, 0...10 V, selectable by DIP-switches
- Accuracy +/- 0,1% of end of scale value
- Supply voltage 115/230VAC, optionally 24VAC/DC
- 2-wire transmitters can be supplied directly by the device
RFID Programmer
type: DEV-RP | ID: ▒
technical features
- Programming device for setting ISO 15693-compatible target devices
- for connection to Windows PC with XP and newer
- Management programm allows three functions:
- Reading mode: read converter
- Writing mode: Write parameters in converterEditing mode: Set parameters for the first time
- Editing mode: Set parameters for the first time